Case Study: Ultra Mag Flow Meter Commissioned for Use with SCADAmetrics Ethermeter

by Jim Mimlitz

A 3" Ultra Mag flow meter is installed into a custody-transfer valve and metering system, then tied into the host SCADA system."


3” Ultra Mag Flow Meter installed into a custody transfer valve and metering system, tied into the host SCADA system


The Ultra Mag®, by McCrometer (Hemet, CA), is an excellent Magnetic Flowmeter for water and wastewater applications; and this article illustrates the installation and commissioning of a 3 inch Ultra Mag, which is then tied into the host SCADA System through a SCADAmetrics EtherMeter® using the Modbus/RTU (RS-485) protocol.

SCADA-Monitored Valve and Master Meter Station

The venue is a custody-transfer valve & metering station, where a large regional water district sells water to a rural municipality.  The station’s meter readings and flow-rates are continuously tracked for the purposes of both operations monitoring and billing; and therefore SCADA readings that match the transmitter readings are absolutely required — often referred to as revenue-grade accuracy.

A legacy turbine-based flow meter at this site had required replacement several times due to mechanical parts wear; and thus the installation of this 100% solid-state flow meter was intended to alleviate such problems in the future.

Ultra Mag flowmeter mechanically installed


It is important to note that when the Ultra Mag is equipped with the “Smart Output” option, then it becomes an AMR/AMI-compatible flow meter, and thus can communicate its Totalizer and Flow-Rate to an EtherMeter-equipped SCADA System or AMR System with Revenue-Grade Accuracy.

The Flow Meter is Mechanically-Installed, But Not Yet Powered-Up or Commissioned. Note that on both the Upstream and Downstream Sides, a Grounding Ring is Installed (each is Sandwiched Between a pair of Full-Flange Rubber Gaskets). McCrometer Packages Two (2) Stainless Steel Grounding Rings with each (Flanged-Version) Ultra Mag Flow Meter.

SCADA-Monitored Ultra Mag flow meter SCADA system with Ultra Mag and Smart Output cable

The Back Cover is Removed, Using an M5 Hex Allen Wrench.

SCADA-Monitored Back Cover


The provided Itron Smart Output Cable was removed, as our personal preference is to use a single cable for both Smart Output and Remote DC Power Input.  The Power and Smart Output Phoenix Headers are Removed, and the Appropriate Wires Are Landed. In this case, we are using General Cable C0764A 8-Conductor, Shielded Cable. Smart Output: RED:Meter.Tx, GRN:Meter.Rx, BLK:Meter.CMN. Power: RED/BLK:+24VDC, WHT/BLK:DC CMN, BLU:GND. The Unused Conductors ORG and WHT were clipped. The DRAIN wire was bonded to Chassis Ground in the SCADA Panel, and Clipped in the Meter Transmitter. Note that McCrometer offers a signal that they call “Smart Output”. This signal is essentially “Sensus Protocol”, and is offered in 6, 8, and 9-digit versions. 9-digits is SCADAmetrics’ preferred configuration.  If the Smart Output must be co-connected to an AMR system, then it is recommended that the user check which configuration is compatible (6, 8, or 9 digits).

Re-Insert Phoenix Headers for Power and Smart Output Signaling; and Seal the Back Cover Using an M5 Hex Allen Wrench. Note that the Original Itron Cable is Replaced with Our 8-Conductor General Cable C0764A, which is carrying both DC Power and Smart Output signaling.

SCADA-Monitored Pre-Connected with Grounding Wires

Un-Bundle the Pre-Connected Convenience Grounding Wires.

SCADA-Monitored Grounding wire connected to the downstream grounding ring


Connect One Convenience Grounding Wire to the Upstream Grounding Ring, and Connect the Other Convenience Grounding Wire to the Downstream Grounding Ring. Add a Mechanical Grounding Lug for External Ground Connection at one of the Grounding Rings (e.g. Burndy Part No. KA8CBAG2R).

McCrometer transmitter with set to Gallons

Interacting with the Integral Keypad and LCD Display, Set the Measurement Units (Tot.MU) to GAL 00001. GAL sets the Meter to Gallons, and 00001 sets the Smart Output to Single-Gallon Resolution. The Pulse Output Parameters Were Not Modified, As the EtherMeter is Only Using the Smart Output, and Not Using the Pulse In This Case. Resolution should be set based on meter size. For 1″ meters and below, 0.1 Gallon Resolution is Recommended. For 1.5″, 2″, and 3″ meters, 1 Gallon Resolution is Recommended. For 4″ and above, 10 Gallon Resolution is Recommended.

The Ultra Mag fully installed and commissioned


The Completed and Fully-Commissioned Installation.

Internal view of the SCADAmetrics control panel


A View of the SCADA Control Panel – Internal View. Note the SCADAmetrics EtherMeter in the Lower Left, Partially Hidden by the UPS Battery Backup.

External view of the SCADAmetrics control panel

A View of the SCADA Panel – External View.

The connected EtherMeter displaying totalization

The Connected EtherMeter displaying the Totalization, which is an exact match to the reading on the McCrometer Transmitter. This reading is collected using the Smart Output signal.

The connected EtherMeter displaying the flow rate


The Connected EtherMeter displaying Flow Rate. This quantity is derived internally in the EtherMeter by calculating delta-Total/delta-Time at periodic intervals.

Do you have an application where you would like to connect your flow meter to a SCADA system?  The McCrometer Ultra Mag flow meter (flanged and insertion models) and McCrometer Propeller flow meters offer industry-standard signal outputs that allow the EtherMeter to tie these meters into Modbus- and Rockwell (Allen Bradley)-based SCADA systems via Ethernet, RS-485, or RS-232 signaling.  Give us a call… We’ll be glad to discuss your application in detail.

Jim Mimlitz